Key Technical Specifications
This GE IS200TREGH1B IS200TREGH1BDB board operates from a 24V DC power supply. It provides 4 emergency trip relay channels for turbine protection. The unit measures 22 cm in length, 16 cm in width, and 4.5 cm in height. Its total weight reaches 0.7 kg without any packaging materials.
The GE IS200TREGH1B IS200TREGH1BDB includes 4 force-guided safety relays for emergency trips. Additionally, it features one 20-pin ribbon connector for host interface. A single 6-pin terminal block connects the DC power input. The board contains 4 safety relays, 4 status LEDs, 4 snubber circuits, 1 watchdog timer, 12 resistors, and 10 capacitors.
| Parameter | Value |
|---|---|
| Power Supply | 24V DC ±10%, 200mA |
| Trip Channels | 4 independent |
| Relay Contact Rating | 5A at 240V AC / 30V DC |
| Response Time | < 10 ms |
| Dimensions (L x W x H) | 22 cm x 16 cm x 4.5 cm |
| Weight | 0.7 kg |
| Relay Type | Force-guided safety relays |
| Status LEDs | 4 units (red when tripped) |
| Power Indicator | 1 LED (green) |
| Host Interface | 20-pin ribbon header |
| Power Connector | 6-pin terminal block |
| Safety Relays | 4 units (force-guided) |
| Snubber Circuits | 4 RC networks |
| Watchdog Timer | 1 unit |
| Resistors | 12 units |
| Capacitors | 10 units |
| Energy Storage | 100 µF at 35V |
GE IS200TREGH1B IS200TREGH1BDB stores energy using one electrolytic capacitor. This capacitor provides 100 µF at 35V rating for relay hold-up. Consequently, the board maintains trip outputs during 25 millisecond power interruptions. Therefore, safety trips remain active through brief voltage dips.
Design and Integration
Both the GE IS200TREGH1B and IS200TREGH1BDB versions share identical safety circuit topology. These boards use four-layer PCB construction with force-guided relay contacts for safety compliance. Consequently, the GE IS200TREGH1B IS200TREGH1BDB operates reliably from -10°C to +55°C ambient temperature.
For installation, you need M3 screws for the four mounting holes. The board draws 150 mA typical current from the 24V DC supply. Each safety relay includes positive-guided contacts for diagnostic coverage. We recommend using 18 AWG wire for all trip output connections.
Practical Application
This emergency trip board initiates turbine shutdown upon detecting critical faults. It receives trip commands from overspeed and vibration protection systems. The GE IS200TREGH1B IS200TREGH1BDB then opens safety relays to de-energize trip solenoids. Therefore, it provides reliable emergency protection for GE turbine control systems.
Details
| Weight | 0.1 kg |
|---|---|
| Dimensions | 25 × 108 × 127 mm |

Reviews
There are no reviews yet.