The IC610MDL126A works as an isolated AC input module for the GE Series One PLC family. It reads high-level AC field signals and delivers clean logic levels to the CPU. Maintenance teams value this unit because each channel isolates the controller from line transients and ground faults.
Channel Configuration and Isolation Design
This module provides eight isolated input channels in a single-slot housing. It accepts 120 VAC nominal signals across an operating range of 0–132 VAC. Each channel carries independent optical isolation, therefore cross-channel interference stays minimal. Furthermore, two isolated groups of four channels simplify field wiring runs. A front terminal strip handles all connections, while the backplane carries status data to the processor.
Dimensions, Weight, and Current Draw
The IC610MDL126A measures 5.1 inches wide, 4.2 inches high, and 1.9 inches deep. It weighs approximately 0.7 pounds, so rack installation remains straightforward. The module draws 80 mA at +5 VDC from the backplane supply. Additionally, it derives field power directly from the AC input lines. Onboard filter capacitors store small charge for transient suppression during switching events.
Key Technical Parameters
| Parameter | Specification |
|---|---|
| Input channels | 8, individually isolated |
| Input voltage | 0–132 VAC |
| Nominal input | 120 VAC |
| Input current | 7 mA per channel typical |
| Isolation | Optical, per channel |
| Dimensions (W×H×D) | 5.1 × 4.2 × 1.9 in |
| Weight | 0.7 lb |
| Backplane current | 80 mA at +5 VDC |
| Operating temperature | 0°C to 60°C |
Response Time and Diagnostic Behavior
Input filtering sets on-state delay near 20 ms, which ignores contact chatter well. Off-state response stays close to 25 ms for reliable release detection. Front LEDs show per-channel status, therefore technicians verify signals without meters. The module reports group status to the CPU through backplane bits.
Application Notes
One backplane slot supports the module in any Series One rack position. Keep 120 VAC field wiring separated from low-level signal cables during routing. Verify terminal torque and channel assignments before you energize the circuit. For high-voltage discrete sensing, the IC610MDL126A delivers per-channel isolation and clear status feedback.
Details
| Weight | 1.5 kg |
|---|---|
| Dimensions | 278 × 194 × 42 mm |



Reviews
There are no reviews yet.