This DYSF118B 61430001-XG communication module connects ABB PLC systems to industrial networks seamlessly. It handles data exchange between controllers, HMIs, and field devices. You can install this unit directly into any compatible ABB rack slot. The module supports multiple protocols for maximum system integration flexibility.
Technical Specifications & Key Parameters
| Parameter | Detail |
|---|---|
| Product Model | ABB DYSF118B 61430001-XG |
| Category | Communication Module |
| Dimensions (H x W x D) | 125 mm x 65 mm x 85 mm |
| Weight | 0.32 kg (0.71 lbs) |
| Communication Ports | One RS-232, one RS-485, one Ethernet |
| Ethernet Speed | 10/100Base-TX (auto-negotiating) |
| Protocol Support | Modbus TCP/IP, Modbus RTU, PROFIBUS DP |
| Baud Rates (Serial) | 9600, 19200, 38400, 57600, 115200 |
| Maximum Nodes | 32 devices on RS-485 multi-drop network |
| Cable Length | 50 feet for RS-232, 4000 feet for RS-485, 100 meters for Ethernet |
| Component Count | 34 ICs, 26 capacitors, 38 resistors |
| Energy Storage | 470 µF capacitor (holds configuration for 12 ms) |
| Operating Voltage | 5V DC from backplane and 24 V DC external |
| Current Draw | 250 mA at 5V DC, 100 mA at 24 V DC |
| Connector Types | One RJ45, one 9-pin D-sub, one 5-pin screw terminal |
| Status LEDs | Power, link, activity, TX, RX, fault |
| Isolation | 1500 V RMS on RS-485 port |
Detailed Feature Overview
ABB DYSF118B 61430001-XG provides three communication ports for network connectivity. The Ethernet port supports Modbus TCP/IP for high-speed data exchange. The RS-485 port handles multi-drop networks with up to 32 devices. The RS-232 port connects to local devices like printers and barcode scanners. Consequently, one module serves multiple communication needs simultaneously.
The module supports Modbus TCP/IP, Modbus RTU, and PROFIBUS DP protocols. You can configure each port independently for baud rate and data format. Baud rates range from 9600 to 115200 for serial connections. A 470 µF capacitor stores configuration settings for 12 milliseconds during power dips. Thirty-four integrated circuits manage protocol conversion and data buffering.
Data Exchange and Diagnostics
The module exchanges data directly with the PLC processor memory. You can map incoming network data to specific register addresses. Outgoing data reads directly from PLC memory locations. Six status LEDs provide clear communication feedback. The LINK LED confirms Ethernet cable connection. The TX and RX LEDs blink during active serial communication.
Installation and Environmental Limits
This module draws 250 mA from the 5V DC backplane supply. It also draws 100 mA from an external 24 V DC supply. Insert the module firmly into any compatible ABB rack slot. Connect Ethernet cable to the RJ45 port for network access. Operating temperature ranges from 0°C to 55°C reliably. Keep humidity below 90% without condensation for long life. The module supports both static and dynamic IP addressing.
Details
| Weight | 0.91 kg |
|---|---|
| Dimensions | 110 × 55 × 90 mm |



Reviews